Custom Sensors CCD8000 Wartungshandbuch Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 49
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
Safety Instructions and Warranty Terms 7
Manual econ sens+ Version 1.40
The econ sens+ energy consumption meter can be used with various public power supplies:
3-phase four-wire power system (with neutral conductor)
3-phase three-wire power system (without neutral conductor)
Single-phase power system
Fig. 7 shows the integration of the econ sens + into a 3-phase 4-wire power system.
The phases L1, L2 and L3 of the voltage path must be protected by means of automatic circuit
breakers to prevent the system from being damaged in the event of a short circuit. A B6 (max. B10)
automatic circuit breaker is recommended. For safety reasons it is preferable to use a short-circuit-
proof conductor (NSGAFÖU) in front of the circuit breakers.
Figure 7: econ sens+ connection diagram to a 3-phase 4-wire power system
Seitenansicht 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 48 49

Kommentare zu diesen Handbüchern

Keine Kommentare