Custom Sensors CCD8000 Wartungshandbuch Seite 31

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 49
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 30
Safety Instructions and Warranty Terms 28
Manual econ sens+ Version 1.40
Frequency drift
The supply frequency is checked. Sudden frequency changes of more than 1Hz of the
nominal supply voltage are detected.
A waveform is stored for this event. Default Value 100%
Vector jump
The 3 supply phases are checked. Jumps of the voltage angle of more than 30° are detected.
A waveform is stored for this event. Default Value 30%
Neutral overvoltage
The neutral voltage is checked. A voltage above 10% of the nominal supply voltage is
detected. Default Value 10%
Power on/off
The last power on and off times are logged.
Harmonic current
The 3 supply phases are checked. Total harmonic distortions of a current above 2% are
detected. A waveform is is stored for this event. Default Value 100%
Time change
Changes to the internal clock time are logged.
Seitenansicht 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 48 49

Kommentare zu diesen Handbüchern

Keine Kommentare